535 User's Manual Chapter 5 47
Controller Set Up
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
▲ ▼
MENU DISPLAYFAST
9. RSP FIXED
Defines what happens if remote setpoint is lost while it is active and then is
restored.
• REMOTE SP Returns to remote setpoint when it is restored
D LOCAL Local setpoint remains active when RSP is
restored
RETRANS.
1. TYPE:2
Defines what is to be retransmitted for output 2
D PV This refers to the linearized process variable
• SETPOINT This is the target setpoint
• RAMP SP This is the ramping, or actual setpoint, when the
setpoint is ramping
• CTRL. OUT This is the control output value
2. LOW RANGE:2
Defines the low end of the range for output 2 in engineering units. Does not appear
for type CTRL.OUT.
R –9999 to 99999
D Dependent on the process variable range
3. HI RANGE:2
Defines the high end of the range for output 2 in engineering units. Does not
appear for type CTRL.OUT.
R –9999 to 99999
D Dependent on the process variable range
4. TYPE:3
Defines what is to be retransmitted for output 3
D PV This refers to the linearized process variable
• SETPOINT This is the target setpoint
• RAMP SP This is the ramping, or actual setpoint, when the
setpoint is ramping
• CTRL. OUT This is the control output value
5. LOW RANGE:3
Defines the low end of the range for output 3 in engineering units. Does not appear
for type CTRL.OUT.
R –9999 to 99999
D Dependent on the process variable range
LO RANGE:2
(D)
TYPE:3
PV
LO RANGE:3
(D)
HI RANGE:2
(D)
RSP: FIXED
LOCAL
RETRANS.
TYPE:2
PV