535 User's Manual Chapter 5 53
Controller Set Up
Access Set Up Return to Operation Next menu Next parameter Next value Access Tuning Return to Operation
+
FAST MENU
DISPLAY
+
MENU MENU
MENU DISPLAYFAST
7. SHED SP
Defines the setpoint status if communications is lost.
D LAST SP Continues to use setpoint that was active prior
to losing communications
DESIG. SP Goes to a designated setpoint value if
communications is lost.
8. DESIG. SP
Defines the value of the designated setpoint if communications is lost.
R Any value in the process variable range
D Dependent on the process variable range
SHED SP
LAST SP
DESIG. SP
(D)