SECTION 6
Status Messages
Status messages are displayed on the TDZ3 or HART Handheld/FDT host whenever there are
events which aect the sensor measurements, conguration or the unit itself.
When one or more failure conditions is detected all error messages will be displayed on the
TDZ3 in a cyclic manner for a period of 2 seconds per message.
Similar information is also provided in the HART status registers.
R
Problem with the RJC Temperature Sensor
DQ (Var
me)
The referenced item (Device, Dynamic or Output Variable) had bad data
quality. Error related to the sensor or output should follow.
SRn
Problem with Sensor n, specific error Message should follow
REn
E
There is a broken wire on the previously referenced sensor. If the specific
broken wire cannot be detected, the messa
e will state 'Wires Broke'
SAT The input is too high for the selected input range
RJC Reference Junction Compensation could not be applied
IL The physical measurement could not be converted to temperature
A Backup device variable (BU1-2, or BU2-1) is mapped as PV, and the primar
sensor has failed
T BCKUP A Backup device variable (BU1-2, or BU2-1) is mapped as PV, and the back
TDZ3 Display Condition
Table 6.1. TDZ
3
or THZ
3
Display Errors- Sensor Data