EasyManua.ls Logo

Morco GB24 - Flue Length Calculation Details; Cutting Horizontal Flue Terminal

Morco GB24
44 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
19
SECTION 5 - INSTALLATION INSTRUCTIONS
5.10 DETERMINING THE FLUE LENGTH
5.11 CUTTING HORIZONTAL FLUE TERMINAL RSF303 (600MM LONG)
10mm
Mark cut length =
A or B + 47mm from terminal lip
1. Measure from the outer terminal lip to end of outer ue. Mark the
required cut length (A or B + 47mm) around the circumference of the
outer ue and cut following the mark to ensure it is cut square.
2. Dress the cut end to make sure all burrs are removed and the cut
edge is in its original shape.
3. Mark the inner tube 10mm longer than the outer tube around its
circumference and cut following the mark to make sure it is cut
square.
4. Remove all burrs and place a light chamfer on the outer edge to aid
assembly.
Centre of turret to edge of turret = 100mm
Turret has a ue insertion of 30mm
The white outer ue tube must protrude the wall by 17mm.
From centreline of turret to wall. Rear mount 155mm, side (including clearance) 200mm
NOTES
REAR
Fit
to wall
A
Flue length measured from outer terminal lip
to end of outer ue
A or B + 47mm
SIDE
Fit
to wall
B
Minimum clearance 2.5mm
WALL
WALL
FIGURE 1
REAR FLUE
Cut ue length = distance from edge of turret to outside of
wall dimension A + 47mm.
Note.MinimumdimensionAwhichcanbeaccommodatedis
91mm.
SIDE FLUE
Cut ue length = distance from edge of turret to outside of
wall dimension B + 47mm.
Note.MinimumdimensionBwhichcanbeaccommodatedis
136mm(withminimumclearanceof2.5mm).

Other manuals for Morco GB24

Related product manuals