EasyManuals Logo

Moxa Technologies ioLogik E1210 Quick Installation Guide

Moxa Technologies ioLogik E1210
2 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
1 2 3
P/N: 1802012001011
ioLogik E1200 Series
Quick Installation Guide
Second Edition, February 2011
1. Overview
The ioLogik E1200 series comes with 2 embedded Ethernet switch
ports that can form a daisy-chain topology, which is the easiest
way to add more Ethernet devices to a network or connect your
ioLogiks in series. Moxa’s free Active OPC Server offers active (or
“push”) communication that works between Moxa’s ioLogik units
and HMI/SCADA systems, providing instant I/O status reports by
“Active Tags.” The event-driven active tags result in an I/O
response time that is 7 times faster than other OPC Server
packages and an 80% reduction in network traffic.
Model Selection:
ioLogik
DI
DO
DIO
Relay
AI
AO
RTD
TC
E1210
16
E1211
16
E1212
8
8
E1214
6
6
E1240
8
E1241
4
E1242
4
4
4
E1260
6
E1262
8
Package Checklist
1 ioLogik E1200 series remote I/O product
Documentation and software CD
Quick installation guide (printed)
2. Specifications
System
Ethernet:
2 x 10/100 Mbps switch ports, RJ45
Protection:
1.5 KV magnetic isolation
Protocols:
Modbus/TCP, TCP/IP, UDP, DHCP, Bootp,
HTTP
Power Input:
24 VDC nominal, 12 to 36 VDC
Wiring:
I/O cable max. 14 AWG
Dimensions:
27.8 x 124 x 84 mm (1.09 x 4.88 x 3.31 in)
Weight:
under 200 g
Operating
Temperature:
Standard Models: -10 to 60°C (14 to
140°F)
Operating
Temperature:
Wide Temperature Models: -40 to 75°C
(-40 to 167°F)
Storage Temperature:
-40 to 85°C (-40 to 185°F)
Ambient Relative
Humidity:
5 to 95% (non-condensing)
Altitude:
Up to 2000 m
Note: Please contact Moxa if you require products guaranteed to
function properly at higher altitudes.
Standards and
Certifications:
UL 508, CE, FCC Class A
Warranty Period:
5 years (excluding ioLogik E1214*)
Details:
See www.moxa.com/warranty
*Because of the limited lifetime of power relay, products that use
this component are covered by a 2-year warranty.
Digital Input
Sensor Type:
NPN, PNP, and Dry contact
I/O Mode:
DI or Event Counter
Dry Contact:
• Logic 0: short to GND
• Logic 1: open
Wet Contact:
• Logic 0: 0 to 3 VDC
• Logic 1: 10 to 30 VDC (DI COM to DI)
Isolation:
3K VDC or 2K Vrms
Counter/Frequency:
250 Hz, power off storage
Digital Output
I/O Mode:
DO or Pulse Output
Pulse Wave
Width/Frequency:
1 ms/500 Hz
Over-voltage
Protection:
45 VDC
Over-current
Protection:
2.6 A (4 channels @650 mA)
Over-temperature
Shutdown:
175°C (typical), 150°C (min.)
Current Rating:
200 mA per channel
Isolation:
3K VDC or 2K Vrms
Relay Output
Type:
Form A (N.O.) relay outputs, 5A
Contact Rating:
5 A @ 30 VDC, 5 A @ 250 VAC, 5 A @ 110
VAC
Inductance Load:
2 A
Resistance Load:
5 A
Breakdown Voltage:
500 VAC
Relay On/Off Time:
1500 ms (Max.)
Initial Insulation
Resistance:
1G min. @ 500 VDC
Expected Life:
100,000 times (Typical)
Initial Contact
Resistance:
30 milli-ohms (Max.)
Pulse Output:
0.3 Hz at rated load
Analog Input
Type:
Differential input
Resolution:
16 bits
I/O Mode:
Voltage / Current
Input Range:
0 to 10 VDC, 4 to 20 mA
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -10 and 60°C
±0.5% FSR @ -40 and 75°C
Sampling Rate (all
channels):
12 samples/sec
Input Impedance:
10M ohms (minimum)
Built-in Resistor for
Current Input:
120 ohms
Analog Output
Resolution:
12 bits
Output Range:
0 to 10 VDC, 4 to 20 mA
Voltage Output:
10 mA (Max.)
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Load Resistor:
• Internal power: 400 ohms
• External 24V power: 1000 ohms
RTD
Input Type:
PT50, PT100, PT200, PT500, PT1000;
Resistance of 10
ohms, 20 ohms, and 100
ohms
Sampling Rate:
12 samples/sec (all channels)
Resolution:
16 bits
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance:
625K ohms
Thermocouple Input
Sensor Type:
J, K, T, E, R, S, B, N
Mili Volt Type:
±78.126 mV, ±39.062 mV, ±19.532 mV
Fault and Overvoltage
protection:
±35 VDC (power off); +30 VDC, -25 VDC
(power on)
Sampling Rate:
12 samples/sec (all channels)
Resolution:
16 bits
Accuracy:
±0.1% FSR @ 25°C
±0.3% FSR @ -40 and 75°C
Input Impedance:
10M ohms
3. Installation
Power and Networking
Connect the +12 to +36 VDC power line to the ioLogik E1200’s
terminal block V+ terminal; connect the ground from the power
supply to the V- terminal. Connect the ground pin ( ) if earth
ground is available.

Other manuals for Moxa Technologies ioLogik E1210

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Moxa Technologies ioLogik E1210 and is the answer not in the manual?

Moxa Technologies ioLogik E1210 Specifications

General IconGeneral
TypeNetwork transmitter & receiver
Maximum transfer distance- m
Mean time between failures (MTBF)671345 h
Operating temperature (T-T)-40 - 167 °F
Cabling technology10/100Base-T(X)
Ethernet LAN (RJ-45) ports2
Input current0.11 A
AC input voltage24 V
Storage temperature (T-T)-40 - 85 °C
Operating relative humidity (H-H)5 - 95 %
CertificationFCC Part 15 Subpart B Class A, IEC 61000-4, IEC 61000-6
Product colorSilver
Weight and Dimensions IconWeight and Dimensions
Depth84 mm
Width27.8 mm
Height124 mm
Weight200 g