If self-defined is selected in
program 5, this program can be set
up. Setting range is from 48.0V to
64.0V. Increment of each click is
0.1V.
If self-defined is selected in
program 5, this program can be set
up. Setting range is from 48.0V to
64.0V. Increment of each click is
0.1V.
When the units are used in parallel
for single phase application, please
select “PAL” in program 28. Please
refer to 5-1 for detailed information.
When the units are operated in 3-
phase application, please choose
“3PX” to define each inverter.
It is required to have at least 3
inverters or maximum 9 inverters to
support three-phase equipment. It’s
required to have at least one
inverter in each phase or it’s up to
four inverters in one phase. Please
refers to 5-2 for detailed
information.
Please select “3P1” in program 28
for the inverters connected to L1
phase, “3P2” in program 28 for the
inverters connected to L2 phase and
“3P3” in program 28 for the
inverters connected to L3 phase.
Be sure to connect share current
cable to units which are on the
same phase.
Do NOT connect share current cable
between units on different phases.