Low DC cut-off voltage:
If battery power is
only power source
available, inverter will
shut down.
If PV energy and
battery power are
available, inverter will
charge battery without
AC output.
If PV energy, battery
power and utility are
all available, inverter
will transfer to line
mode and provide
output power to loads.
If self-defined is selected in
program 5, this program can be set
up. Setting range is from 40.0V to
54.0V. Increment of each click is
0.1V. Low DC cut-off voltage will be
fixed to setting value no matter
what percentage of load is
connected.
auto-charging time
(default)
If “User-Defined” is selected in program 05, this program can be
set up. Setting range is from 5min to 900min. Increment of each
click is 5min. Otherwise, Keeping auto-charging time.
Battery equalization enable
Battery equalization disable
(default)
If “Flooded” or “User-Defined” is selected in program 05, this
program can be set up.
Battery equalization voltage
Setting range is from 48.0V to
64.0V. Increment of each click is
0.1V.
Setting range is from 5min to
900min. Increment of each click is
5min.