22
36
Battery equalized timeout
120min (default)
Setting range is from 5min to 900
min. Increment of each click is 5
min.
37
Equalization interval
30days (default)
Setting range is from 0 to 90 days.
Increment of each click is 1 day
39
Equalization activated
immediately
Disable (default)
Enable
If equalization function is enabled in program 33, this program
can be set up. If “Enable” is selected in this program, its to
activate battery equalization immediately and LCD main page will
shows “ . If “Disable” is selected, it will cancel equalization
function until next activated equalization time arrives based on
program 37 setting. At this time, “ ” will not be shown in LCD
main page.
40
Reset all stored data for PV
generated power and
output load energy
Not reset(Default)
Reset
93
Erase all data log
Not reset(Default)
Reset
94
Data log recorded interval
*The maximum data log
number is 1440. If its over
1440, it will re-write the
first log.
3 minutes
5 minutes
10 minutes(default)
20 minutes