5 Installation and commissioning
46 BA5831400-00 EN
4. Ensure that the cable for the protective conductor is 50mm longer and
equip the conductor with a ferrule.
Figure24: Stripping the cable jacket and wire insulation (example)
5.4.4.1 Standard cable gland
1. NOTICE! If the cable gland is not used, equip it with a sealing plug or re-
place the entire cable gland with a dummy plug in order to ensure the IP
degree of protection.
2. Remove the locking screw on the adapter.
Figure25: Removing the locking screw