9 Appendix: General Certification Information
The S5000 Transmitter, S5000 Junction Box, and Digital Sensor have the following certifications/approvals: ATEX, IECEx,
CSA, FM,INMETRO, DNGL Type Approval. They also comply to the EMC, Radio Equipment and Marine Equipment
Directives. The S5000 Transmitter and Junction Box have a Type 4X and IP66 environment rating.
S5000 Transmitter, Junction Box, and JB5000 Junction Box
U.S. Division Hazardous Locations as defined by the NEC
Class I, Division 1, Groups A, B, C, D; T5/T6*
Class I, Division 2, Groups A, B, C, D; T4/T6*
Class II, Division 1,2 Groups E, F, G; Class III, Division 1,2; T6 (T5 under FMApproval)
NOTE: See CSA Certificate for detailed certification information including possible
limitations to the above information. FMApproval does not include Zone classified
locations.
*Applicable to S5000 Junction Box only
U.S. Zone Hazardous Locations as defined by the NEC
Class I, Zone 1, AEx db IIB+H
2
T5/T6* Gb
Class I, Zone 2, AEx nA nC** IIC T4/T6* Gc
Zone 21, AEx tb IIIC T85°C Db
NOTE: See CSA Certificate for detailed certification information including possible
limitations to the above information. FM Approval does not include Zone classified
locations.
*Applicable to S5000 Junction Box only
**nC not applicable to S5000 Junction Box
Canadian Division Hazardous Locations as defined by the CEC
Class I, Division 1, Groups A**, B, C, D; T5/T6*
Class I, Division 2, Groups A, B, C, D; T4/T6*
Class II, Division 1,2 Groups E, F, G; Class III, Division 1,2; T6
NOTE: See CSA Certificate for detailed certification information including possible
limitations to the above information.
*Applicable to S5000 Junction Box only
**Applicable for cemented window covers only
Canadian Zone Hazardous Locations as defined by the CEC
Ex db IIB+H
2
T5/T6* Gb
Ex nA nC** IIC T4/T6* Gc
Ex tb IIIC T85°C Db