Figure D-2 NEMA 4X Mounting Screws and Cable Locations
NEMA 7 Model:
1. Disconnect AC power from the Level Plus monitor at the main fuse panel.
2. The main electronics assembly must be removed from the NEMA 7 enclosure to gain access to the EPROM
devices. Follow steps 3 through 8 to remove the main electronic assembly.
3. Disconnect the AC power terminations at terminal block TB1.
4. Disconnect any customer terminations to the relay contacts (TB3) and to the communication interface (TB2).
Terminal blocks TB2 and TB3 are of the pluggable type.
5. Disconnect the tank gauge field wiring from intrinsic safety barriers.
6. Remove the six mounting screws (and lock washers) that secure the electronic assembly to the aluminum brack-
ets in the NEMA 7 enclosure. See illustration D-3. Do not remove the four screws that hold the aluminum brack-
ets to the back of the NEMA 7 enclosure.
Heater Cable
4-20 mA
Cable
Intrinsic Safety
Barrier Ground
Terminal
P3
4-20 mA
Terminal Block
Communications
Terminal Block (TB2)
Relay Terminal
Block (TB3)
Tank Gauge
Field Wiring
Cables
Terminal Block
Cover
Enclosure AC
Ground Cable
Heater Cable
Connector
AC Power
Terminal
Block (TB1)
Power
Alarm
1
2 3 4 5
±
Mode
Clear
Fnctn
Enter
0
9
8
7
6
LEVEL PLUS
¤
TANK MONITORING SYSTEM
l
Panel Mounting
Screws (4 total)
S1
F1
F2
97