Register 11 general format (Product level, interface level and average temperature).
<STX>atrr:dddddddddd:dddddddddd:dddddddddd<ETX>cc
<STX> = ASCII start of text character (02 Hex)
a = Level Plus communication address
t = Tank number
rr = Register number
: = ASCII colon field delimiter (3A Hex)
d = data (fixed at 3 data fields, 10 characters for each data field)
<ETX> = ASCII end of text character (03 Hex)
cc = optional 2 byte checksum (if enabled)
Register 11 output example from monitor at communication address C, Tank 3.
<STX>C311:129.586~~~:11.555~~~~:83.1~~~~~~<ETX>
Register 12 general format (Individual RTD temperatures).
<STX>atrr:dddddd:dddddd:dddddd:dddddd:dddddd<ETX>cc
<STX> = ASCII start of text character (02 Hex)
a = Level Plus communication address
t = tank number
rr = register number
: = ASCII colon field delimiter (3A Hex)
d = data (fixed at 5 data fields, 6 characters for each data field)
<ETX> = ASCII end of text character (03 Hex)
cc = optional 2 byte checksum (if enabled)
Register 12 output example from monitor at communication address D, Tank 4.
<STX>D412:78.2~~:79.6~~:80.4~~:81.2~~:82.5~~<ETX>
Register 13 general format (System alarms).
<STX>atrr:dddddddddddddddd<ETX>cc
<STX> = ASCII start of text character (02 Hex)
a = Level Plus communication address
t = tank number
rr = register number
: = ASCII colon field delimiter (3A Hex)
d = data (fixed at 1 data field of 16 characters)
<ETX> = ASCII end of text character (03 Hex)
cc = optional 2 byte checksum (if enabled)