MD-1000I / MD-2000I / MD-3000I Technical Information
Battery mode: output circuit breaker
EPO UPS shuts down immediately
Normal mode Transfer to bypass mode Excessive
temperature
Battery mode UPS shuts down immediately
Audible alarm
Battery mode Audible signal every 1.5 seconds once
Weak battery Audible signal every 0.2 seconds once
Overload Audible signal every 3 seconds once
Failure Continuous audible signal
(or every 3 seconds once)
Physical
Dimensions (HxWxD in mm) 88(2U)x440x
405
88(2U)x440x
650
88(2U)x440x
650
Weight 15.7kg 29.4kg 29.7kg
Input connector 10A, IEC
320-C14
10A, IEC 320-
C14
16A, IEC
320-C20
Output connector (6) 10A,IEC 320-C13 (4) 10A,IEC
320-C13
(1) 16A,IEC
320-C19
Environmental
Operating temperature 0-40
Noise level <50dBA
Relative humidity 0 to 90% (without condensation)
Interfaces
Type 1 *USB port and 1*RS-232 port
SNMP (optional) Energy management by SNMP manager and
Web browser
Operating systems Windows 95/98/NT/2000/XP Novell NetWare,
Linux, etc.
Standards and certification
Safety IEC/EN 62040-1-1,IEC 60950-1
Performance IEC/EN 62040-3
EMC IEC/EN62040-2 Class A, FCC Part 15
Safety CE,UL, cUL, FCC
MD Series 88