MODBUS (MFM 13-M1)
Access
Type
Parameter
Register
Data Type
Float
R kWh Value *
0
2
Volt
Kilo Volt
Value
0
1
Selection
Slave Address :
Parity :
Read Function Register :
Write Function Register :
Baudrate :
Datatype :
1 to 125
None,Even,Odd
0x03 and 0x04
9600,4800,19200,38400bps
Float
0x06 and 0x10
Sr.No
1
R
R
Voltage L1-N Value
V L1-N Unit
12
14
4
5
R
4
6
2
kVAh Value *
R kvarh Value *
8
10
3
N1
N1
N1
*Note 1 :- In Above Energy Parameter, Energy Value
Representation shown as per below.
Example :- Actual Value = 320126789.321
Above Register Address 1 = 320126789
Below Register Address 2 = 0.321
Volt
Kilo Volt
Value
0
1
Selection
R
R
Voltage L2-N Value
V L2-N Unit
16
18
6
7
Volt
Kilo Volt
Value
0
1
Selection
R
R
Voltage L3-N Value
V L3-N Unit
20
22
8
9
Volt
Kilo Volt
Value
0
1
Selection
R
R
AVG VLN Value
AVG VLN Unit
24
26
10
11
Value
0
Selection
R
R
Current L1 Value
Current L1 Unit
44
46
20
21
Value
0
Selection
R
R
Current L2 Value
Current L2 Unit
48
50
22
23
Value
0
Selection
R
R
Current L3 Value
Current L3 Unit
52
54
24
25
Ampere
Value
0
Selection
R
R
AVG Current Value
AVG Current Unit
56
58
26
27
Volt
Kilo Volt
Value
0
1
Selection
R
R
Voltage L12 Value
V L12 Unit
28
30
12
13
Volt
Kilo Volt
Value
0
1
Selection
R
R
Voltage L23 Value
V L23 Unit
32
34
14
15
Volt
Kilo Volt
Value
0
1
Selection
R
R
Voltage L31 Value
V L31 Unit
36
38
16
17
Volt
Kilo Volt
Value
0
1
Selection
R
R
AVG VLL Value
AVG VLL Unit
40
42
18
19
Ampere
Ampere
Ampere
R
Line 1 Power Factor 60
28
R
62
29
R
64
30
Line 2 Power Factor
Line 3 Power Factor
R
66
31
R
68
32
System Power Factor
Average Power Factor
R
70
33
System Frequency
Access
Type
Parameter
Register
Data Type
Float
Sr.No
kW
MW
Value
1
2
Selection
R
R
Line 1 kW value
Line 1 kW Unit
72
74
34
35
kW
MW
Value
1
2
Selection
R
R
Line 2 kW value
Line 2 kW Unit
76
78
36
37
kW
MW
Value
1
2
Selection
R
R
Line 3 kW value
Line 3 kW Unit
80
82
38
39
kW
MW
Value
1
2
Selection
R
R
Total kW
Total kW Unit
84
86
40
41