Do you have a question about the MULTISPAN UTC - 413P and is the answer not in the manual?
Input Type | Thermocouple, RTD |
---|---|
Number of Inputs | 1 |
Control Mode | PID, On/Off |
Mounting | Panel Mount |
Output | Relay |
Power Supply | 100-240 VAC |
Display | LED |
Communication | RS485 Modbus |
Control Output Current | 3A |
3 Digit 7 seg 0.56", red LED Display.
Unit dimensions 48x48x70mm, panel cutout 45x45mm.
Selectable J, K, PT-100 sensors with specific temperature ranges.
PID/ON-OFF selectable control with relay and SSR outputs.
100-270V AC power, IP-65 front, 0-55°C operating temp, 95% RH.
Follow all safety codifications, symbols, and instructions for safe operation.
Risk of electric shock; ensure power is OFF before wiring.
Keep power OFF during wiring; do not touch terminals when power is supplied.
Use adequate rated wires with twists for shortest connections to reduce EMI.
Use 1mm² or greater cross-section cables with at least 1.5kV insulation.
Use compensation wires for thermocouples and low-resistance wires for RTDs.
Standard power supply cables improve anti-noise effect.
Built-in type installation; terminals may not be accessible post-installation.
Avoid metal pieces or debris entering the product to prevent safety hazards.
Install a circuit breaker or mains switch for power ON/OFF control.
Use and store the instrument within specified ambient temperature and humidity.
Prepare panel cutout as shown and fit unit using clamps.
Avoid installing near heating sources, caustic vapors, or steam.
Use M3.5 crimp terminals and tighten screws to 1.2 N.m.
Do not connect anything to unused terminals.
Clean regularly with a soft cloth; avoid isopropyl alcohol or other agents.
Fusible resistor must not be replaced by the operator.
Use SET, UP, DOWN keys for parameter setting and saving.
Press UP key for 6 seconds to start or stop PID auto-tuning.
Press UP + DOWN keys for 3 seconds to enter factory setting mode.
Press SET key for 3 seconds to enter password parameter.
Enter password '050' to proceed to basic configuration.
Enter '73' to access basic configuration settings.
Select input type (J, K, PT-100) using UP/DOWN keys.
Set the offset value for the input sensor.
Configure Set Point Low Limit (SLL) and Set Point High Limit (SHL).
Choose between PID and ON-OFF control actions.
Select Relay Mode (HE for Heat, COL for Cool).
Enter '37' to access control parameter settings.
Configure Proportional Band (PB), Integral Time (IT), Derivative Time (DT).
Set Cycle Time (CT) and adjust Manual Reset (MR).
Configure Hysteresis and Delay Time for control output.
Press UP + DOWN keys for 3 seconds to enter factory setting mode.
Use UP + DOWN keys to apply factory set values or escape.
Table lists default SR, Parameter (PB, IT, DT, CT, MR, OFFSET, HYSTERESIS, DELAY TIME) and Values.