EasyManuals Logo

Munters ComDry M210X User Manual

Munters ComDry M210X
32 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #28 background imageLoading...
Page #28 background image
9.4. Technical data
Process air
(1)
Free-blowing air 50/60 Hz (m³/h) 240
Rated airflow at 60 Pa (m³/h) 210
Max. static pressure 50/60 Hz (Pa) 300
Fan motor power (kW) 0,09
Reactivation air
(1)
Rated airflow at 70 Pa (m³/h) 25
Max. static pressure (Pa) 250
Fan motor power (kW) 0,08
Reactivation air heater
Heater power (kW) 0,84
Factory set reactivation temperature (Rt) limit (°C) 130
Factory set wet air temperature (Wt) limit (°C) 75
Temperature increase across heater (°C) 100
Other
Sound pressure level, free blowing process fan (dBA) 58
IEC protection class (unit) IP33
IEC protection class (electrical panel) IP54
Fan motor winding insulation class Class B
Drive motor winding insulation class Class B
Rotor type HPS
Environmental conditions
Operating temperature (°C) -20... +40
Maximum installation altitude, above sea level (m) 2000
Transport and storage temperature (°C) -20... +70
Total power, voltage and current
Voltage (V) 115 230
Frequency (Hz) 50/60 50/60
Total power (W) 1010 1010
Current (A) 8,8 4,4
Fuse 3 AG, 250 VAC, 10
A Slow
3 AG, 250 VAC, 6 A
Slow
(1)
The specified performance is based on 20 °C and air density of 1.2 kg/m³.
ComDry M210X Dehumidifier
28

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Munters ComDry M210X and is the answer not in the manual?

Munters ComDry M210X Specifications

General IconGeneral
BrandMunters
ModelComDry M210X
CategoryDehumidifier
LanguageEnglish

Related product manuals