MCS300
10Technicalspecication
TechnicaldataMCS300230V/50Hz115V/50Hz115V/60Hz
Processair
(1)
Systemairow(m³/h)
330330330
Nominalairowwithducting(m³/h)
300300300
Minimumavailablestaticpressure(Pa)
200200200
Reactivationair
(1)
Nominalairowwithducting(m³/h)
604760
Minimumavailablestaticpressure(Pa)
200200250
Fanmotor
Motor,power(kW)
0,150,150,15
Motor,current(A,1~)
1,052,12,1
Drivemotor
Motor,power(kW)
0,0020,0020,002
Motor,current(A,1~)
--.-
Reactivationheater
Reactivationheater,power(kW)
2,01,51,5
Temperatureincrease(°C)
957373
Electricalpowerandnominalcurrent(kW)
Maximumelectricalpower(kW)
2,21,71,7
Filter
Filterkit(ArticleNo.)130025/1KIT130025/1KIT130025/1KIT
Temperaturerange
Permittedambientoperatingtemperature
-20to+40°C-20to+40°C-20to+40°C
Otherdata
Protectionform
IP44IP44IP44
FanmotorwindinginsulationclassFFF
Maximumsoundlevelwithoutducting(dBA)
Max.60,0Max.60,0Max.60,0
Totalunitweight(kg)
252525
Rotortype
HPSHPSHPS
Dimensions
Depth(mm)
400400400
Width(mm)
400400400
Height(mm)
550550550
1)
Thespeciedguresarenominalvaluesbasedoninlettemperaturesatthefansof20°Candanairdensityof1,2kg/m
3
.
Table10.1Technicalspecication
190TEN-1027-F1404Technicalspecication22