5Commissioning
Priortostartingforthersttime,someoperatingparametersmustbesetinthecontrolsystem,seechapter
6.4,Operatorpanel.
Somefeaturesrequireconnectionofexternalequipment.Forwiringdetails,seethewiringdiagram.
5.1Pre-startchecks
W W
W
ARNING! ARNING!
ARNING!
Installation,adjustments,maintenanceandrepairsmustonlybecarriedoutbyqualiedpersonnelwhoare
awareoftherisksinvolvedwhenworkingwithequipmentoperatingwithhighelectricalvoltageandhighmachine
temperatures.
Beforestartingthedehumidierforthersttime,ensurethatthemainspowersupplyisisolatedfromthe
dehumidierandcarry-outthefollowingchecks:
1.CheckthattheModeswitchonthedehumidierisinthe“OFF”position,seesection6.4,Operatorpanel.
2.Checktheairintakeltersfordamageandproperxationandalsocheckthatallareasinsidetheunitare
clean.
3.Visuallyinspectallductingandductconnectionstomakesurethatallconnectionshavebeencorrectly
installedandthattherearenosignsofdamagetothesystem.Alsocheckthatallductsarefreefrom
obstaclesblockingtheairpassage.
4.Removethetoppanelandcheckthatnoneofthemaincontactbreakersintheelectricaloperatorpanel
havebeentripped.Fordetailsrefertothewiringdiagramsprovidedwiththeunit.
5.Checkthattheincomingpowersupplyvoltageiscorrectandthatthecablesarecorrectlyconnected.
6.TheML270hasa3phasefanmotorandtherotationdirectionofthefanimpellermustbecheckedafter
connectiontothepowersupply.Openthefrontpanelofthedehumidierandtakeouttheprocesslter.
Startthedehumidierandcheckthatthefanimpellerisrotating.Switchoffthedehumidierandwatch
thefanimpellerjustbeforeitstopsrotating.Checkthatitisrotatingclockwise.
7.Ifanexternalhumiditysensorisused,checkthatthesensoriscorrectlypositionedintheroomandis
correctlyconnectedtotheunit,seesection4.8,Externalhumiditysensor.
8.Settheprocessandreactivationairowdamperstothefullyopenposition.