76 V 1.9
DIO8(DIO8) Art. No. 55289
Bus Data
Transfer protocol ............................................... PROFINET I/O
Transfer rates .................................................... 100 Mbit/s
Addressing ......................................................... via DHCP
S
upply
Operating voltage U
B
......................................... 24 V DC
Supply voltage range ......................................... 18 ... 30 V DC
Current consumption (without inputs) ............... < 150 mA at 24 V DC
Sensor supply .................................................... max. 200 mA per sensor
Short-circuit protection for sensors ................... Multifuse,
............................................................................ up to 100 mA load automatic start
............................................................................ from 100 mA load reset required
Tripping time multifuse ...................................... 1s at I
K
1 A and 23°C
Reverse polarity protection inputs ..................... Yes
I
nputs / diagnostics
Max. no. of inputs ............................................... 16
Delay time with signal change ........................... 2 to 5 ms
Input characteristics .......................................... EN 61131-2, type 2
Input filter ............................................................ approx. 1 ms
Over voltage protection ...................................... Yes (suppressor diode)
R
everse polarity protection
Module electronics ............................................. Yes
Sensors .............................................................. No
Actuators ............................................................ No
O
utputs
Max. no. of outputs ............................................. 16
Nominal current .................................................. 1.6 A
Max. total current ................................................ 9 A
Over voltage protection ...................................... Yes (suppressor diode)
Cable length ....................................................... 0.75 mm² max. 10 m
............................................................................ 0.34 mm² max. 5 m
Cable diameter ................................................... max. 1.5 mm²
Signal delay ........................................................ 2 to 5 ms
Max. switching frequency at inductive load ........ 20 Hz
Max. lamp load ................................................... 10 W