EasyManua.ls Logo

Murr Elektronik 55283 - Page 77

Murr Elektronik 55283
79 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Manual for MVK-MPNIO Modules
V 1.9 77
DI8 DO8 FSU Art. No. 55339
Bu
s Data
Transfer protocol ................................................ PROFINET I/O
Transfer rates ..................................................... 100 Mbit/s
Addressing ......................................................... via DHCP
FSU (Fast-Start-Up) ............................................ < 500 ms
S
upply
Operating voltage U
B
......................................... 24 V DC
Supply voltage range ......................................... 18 ... 30 V DC
Current consumption (without inputs) ................ <150 mA at 24 V DC
Sensor supply .................................................... max. 200 mA per sensor
Short-circuit protection for sensors .................... Multifuse,
Tripping time multifuse ....................................... 1s at I
K
1 A and 23 °C
Reverse polarity protection inputs ..................... Yes
I
nputs / diagnostics
Max. no. of inputs ................................................ 8
Delay time with signal change ........................... 2 to 5 ms
Input characteristics ........................................... EN 61131-2, type 2
Input filter ............................................................ approx. 1 ms
Over voltage protection ....................................... Yes (suppressor diode)
Reverse polarity protection
Module electronics .............................................. Yes
Sensors ............................................................... Yes
Actuators ............................................................. Yes
O
utputs
Max. no. of outputs ............................................. 8
Nominal current ................................................... 2.0 A
Max. total current ................................................ 9 A
Over voltage protection ....................................... Yes (suppressor diode)
Cable length ........................................................ 0.75 mm² max. 10 m
............................................................................ 0.34 mm² max. 5 m
Cable diameter .................................................... max. 1.5 m
Signal delay......................................................... 2 to 5 ms
Max. switching frequency at inductive load ........ 20 Hz
Max. lamp load .................................................... 10 W