EasyManua.ls Logo

Nastec MIDA 207 - Control Parameters: COMBO and PI Control

Default Icon
56 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Default Description 1 2 3 4 5
Control ramp
t = XX [s]
40 Time in which the device decreases the motor power frequen-
cy from the minimum control frequency (Frequency min con-
trol) to the minimum motor frequency (Min motor frequency).
If during this time the measured value falls below Set value -
Delta control, the device restarts the motor. If not, the device
will stop the motor completely following the control ramp (Con-
trol ramp).
x x
Delta start
p = XXX.X [bar]
0.5 This parameter communicates by how much the measured
value must fall from the set value for the previously stopped
pump to be restarted.
x x
Delta control
p = XXX.X [bar]
0.1 This parameter communicates by how much the measured
value must fall in relation to the set value so that the pump,
during shutdown in control ramp, is restarted.
1: Min motor frequency; 2: Frequency min control; 3: Delta
control; 4: Set value ; 5: Stop delay; 6: Control ramp
x x
Delta stop
p = XX.X [bar]
0.5 This parameter represents the increment of the measured val-
ue with respect to the set value that must be exceeded so that
a forced shutdown of the pump according to the stop ramp can
occur.
x x
Ki
XXX
Integral coefficient used in constant value adjustment. x x
Kp
XXX
Proportional coefficient used in constant value adjustment. x x
COMBO
ON/OFF
OFF Enable the function COMBO for the combined operation of
several pumps in parallel. Read the dedicated chapter.
x x
Address
XX
01 Device address when in COMBO mode:
0: master
01 to 07: slave
x x
Alternance
ON/OFF
ON Enabling the alternation between units in COMBO and D.O.L.
The order of priority of operation is alternated based on the
previous start-up of each pump in order to obtain an almost
uniform wear of the pumps.
x x
Alternance period
t = XX [h]
0 Maximum difference in operating hours between multiple devi-
ces in the unit.
0 means 5 minutes.
x x
COMBO synchrony
ON/OFF
OFF Through this parameter it is possible to activate the synchro-
nous operation of the pumps in COMBO. Read the dedicated
chapter.
However, it is necessary to lower parameter Frequency min
controlaccordingly.
x x
Start delay AUX
t = XX [s]
00 Time delay with which the pumps in a group start up after
the variable speed pump has reached the maximum motor
frequency and the measured value has fallen below the differ-
ence Set value - Delta control.
x x
PI control
Direct/Reverse
Direct PI control mode:
Direct: as the pump speed increases, the measured value
increases.
Reverse: as the pump speed increases, the measured value
decreases.
x x
Periodic autorun
t = XX [h]
00 Periodic pump start-up after X hours of inactivity. The value 0
disables the function.
x x x x x
MIDA
35

Table of Contents

Other manuals for Nastec MIDA 207

Related product manuals