Chapter 7 Counters
© National Instruments Corporation 7-3 M Series User Manual
Figure 7-3. Single Point (On-Demand) Edge Counting with Pause Trigger
Buffered (Sample Clock) Edge Counting
With buffered edge counting (edge counting using a sample clock), the
counter counts the number of edges on the Source input after the counter is
armed. The value of the counter is sampled on each active edge of a sample
clock. A DMA controller transfers the sampled values to host memory.
The count values returned are the cumulative counts since the counter
armed event. That is, the sample clock does not reset the counter.
You can route the counter sample clock to the Gate input of the counter. You
can configure the counter to sample on the rising or falling edge of the
sample clock.
Figure 7-4 shows an example of buffered edge counting. Notice that
counting begins when the counter is armed, which occurs before the first
active edge on Gate.
Figure 7-4. Buffered (Sample Clock) Edge Counting
Counter Armed
SOURCE
Pause Trigger
(Pause When Low)
Counter Value
100 5432
3
6
3
Counter Armed
SOURCE
Sample Clock
(Sample on Rising Edge)
Counter Value
Buffer
10763452

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the National Instruments M Series and is the answer not in the manual?

National Instruments M Series Specifications

General IconGeneral
BrandNational Instruments
ModelM Series
CategoryMedia Converter
LanguageEnglish

Related product manuals