SKE4 Steam Humidifier
BACnet Communication Module User Guide
Device Object Properties
The following table lists all the BACnet properties supported for the device object. The W indicates that the property is
writable using the BACnet WriteProperty service.
Table 2 - Device Object Properties
• Programmable where the instance part of the Object_Identifier is in the range of 0-4194302
• The device instance must be unique system-wide
• The default value for the device instance= 153001 (Vendor_Identifier*1000 + MAC)
SKE4, programmable up to 32 Bytes
Programmable up to 32 Bytes (default: SKE4 Controller)
Application_Software_Version
Default 0; incremented if Object Name, Object List and/or device ID change
2015-01-01 (Thu), 00:00:00:00
Protocol_Services_Supported
• confirmedCOVNotification
• subscribeCOV
• atomicReadFile
• atomicWriteFile
• readProperty
• readPropertyMultiple
• WriteProperty
• writePropertyMultiple
• deviceCommunicationControl
• reinitializeDevice
• i-Am
• i-Have
• unconfirmedCOVNotification
• unconfirmedPrivateTransfer
• timeSynchronization
• who-Has
• who-Is
• utcTimeSynchronization
• subscribeCOVProperty
Protocol_Object_Types_Supported
• analog-input
• analog-output
• analog-value
• binary-input
• binary-output
• binary-value
• device
• file
• group
• multi-state-input
• multi-state-output
• program
• Schedule
• multi-state-value
• characterstring-value
• date-value
• datetime-value
• positive-integer-value
• time-value
Programmable in the range of 1 to 127 (default: 127)
Empty by default. COV subscription will be lost on a power cycle.
List of properties that exist within the object.