SKE4 Steam Humidifier
BACnet Communication Module User Guide
Object Types Supported
The following table lists all the BACnet properties supported for each object type. Most of the properties are locked.
The exception is Present_Value, which represents the dynamic operating values of the device, and the Status_Flag,
Event_State, and Reliability properties, which reflect the availability of the Present_Value. Unless otherwise specified,
properties are not changeable.
Table 3 - Object Types Supported
Optional Properties
Supported
Note: Writable properties are different for some objects. Refer to the respective Object Table information to know the writable property for objects.
• Reliability
• Description
• Min_Present_Value
• Max_Present_Value
• Resolution
• COV_Increment
• Out_of_Service
• COV_Increment
• Units
If "Out_of_Service" is true, Present_Value becomes
a writable property. Refer to Out_of_Service
Property section on page 7 for more information.
• Reliability
• Description
• Min_Present_Value
• Max_Present_Value
• Resolution
• COV_Increment
• Priority_Array
• Relinquish_Default
• Present_Value
• Out_of_Service
• COV_Increment
• Relinquish_Default
• Units
Refer to Out_of_Service Property section on page 7
for more information.
• Description
• Reliability
• Min-Pres-Value
• Max-Pres-Value
• Resolution
• COV_Increment
• Present_Value
• COV_Increment
• Out_of_Service
• Relinquish_Default
• Units
• Reliability
• Active_Text
• Inactive_Text
• Description
• Out_of_Service
• Polarity
• If "Out_of_Service" is true, Present_Value
becomes a writable property. Refer to
Out_of_Service Property section on page 7 for
more information.
• Reliability
• Active_Text
• Inactive_Text
• Description
• Priority_Array
• Relinquish_Default
• Minimum_Off_Time
• Minimum_On_Time
• Present_Value
• Out_of_Service
• Relinquish_Default
• Minimum_Off_Time
• Minimum_On_Time
Refer to Out_of_Service Property section on page 7
for more information.
• Description
• Reliability
• Inactive-text
• Active-text
• Minimum_Off_Time
• Minimum_On_Time
• Present_Value
• Out_of_Service
• Polarity
• Relinquish_Default
• Minimum_Off_Time
• Minimum_On_Time
• Max_Master
• Max_Info_Frame
• Description
• active-COV-subscriptions
• Local_Time
• Local_Date
• UTC_Offset
• Daylight_Savings_Status
• Backup_Failure_Timeout
• Configuration_Files
• Last_Restore_Time
• Backup_And_Restore_State
• Backup_Preparation_Time
• Restore_Completion_Time
• Restore_Preparation_Time
• Location
• Serial_Number
• Profile_Name
• Object_Identifier
• Object_Name
• Max_Master
• Description
• Local_Time
• Local_Date
• UTC_Offset
• Daylight_Savings_Status
• Apdu_Timeout
• Backup_Failure_Timeout
• Location
Only 0 is the accepted value to be written to the file
size.