4.2.1 Aux enable
Default value
Values (Modbus value)
Single
Single (1), Parallel (2)
Unit
LCD name
Modbus address
NA
Aux enable
0x102C
Enable/Disable auxiliary output.
4.2.2 PC shutdown enable
Default value
Values (Modbus value)
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
NA
PC shutdown enable
0x1030
See §3.1.5.
4.2.3 PC automatic restart enable
Default value
Values (Modbus value)
Disabled
Disabled (0), Enabled (1)
Unit
LCD name
Modbus address
NA
PC restart enable
0x1031
See §3.1.5.
4.2.4 PC shutdown delay
Default value
Range
Resolution
3600s
1…3600s
1s
Unit
LCD name
Modbus address
Seconds
PC shutdown delay
0x1032
See §3.1.5.
4.2.5 PC shutdown time
Default value
Range
Resolution
600s
1…600s
1s
Unit
LCD name
Modbus address
Seconds
PC shutdown time
0x1033
See §3.1.5.
4.2.6 PC restart minimum time
Default value
Range
Resolution
1s
1…60s
1s
Unit
LCD name
Modbus address
Seconds
PC restart time
0x1034
See §3.1.5.
4.2.7 PC off detection current threshold
Default value
Range
Resolution
0A
0…20A
0.1A
Unit
LCD name
Modbus address
Amperes
PC OFF I
0x1035
See §3.1.5.
DCW20_040-02-700-005-EH-1117