3.5 Modbus
DCW20 communicates through Modbus/RTU as specified on “MODBUS over Serial Line” and
“MODBUS APPLICATION PROTOCOL SPECIFICATION” documents available on
http://www.modbus.org/.
Table 2 contains the field types and Table 3 the mapped fields. For types bigger then 16bit, access all
registers in one transaction (multiple register read or write) to ensure atomic operation.
Single bit with value 0 or 1
Signed 16 bit value (2’s complement)
Signed 32 bit value (2’s complement) Composed of 2 consecutive
registers in big-endian order.
Unsigned 32 bit value. Composed of 2 consecutive registers in big-
endian order.
Time and date field. Composed of 4 Modbus registers as follows:
Hour of the day (24h format)
Modbus baudrate.
1: 9600 baud
2: 19200 baud
3: 38400 baud
4: 57600 baud
5: 115200 baud
Modbus parity.
1: None
2: Even
3: Odd
Battery type.
1: Lead
2: Nickel
DCW20_040-02-700-005-EH-1117