DCW20 User Manual rev. 5
Page 16/34
Address
Type
R/W
Unit
Min.
Max.
Description
3: Lithium
4: Supercapacitor
0x1011
UINT16
R/W
0.1V
10
58
Battery charge voltage.
0x1012
UINT16
R/W
0.1A
0.5
20
Battery charge current.
0x1013
UINT16
R/W
0.1V
10
58
Battery float voltage.
0x1014
UINT16
R/W
0.1V
5
58
Battery low voltage.
0x1015
UINT16
R/W
0.1V
5
58
Battery deep discharge voltage.
0x1016
UINT16
R/W
0.1A
5
21
Battery max. discharge current.
0x1017
UINT16
R/W
0.1Ah
1
200
Battery capacity - Supercap
capacitance.
0x1018
SINT16
R/W
1°C
-40
60
Battery min. temperature.
0x1019
SINT16
R/W
1°C
-40
60
Battery max. temperature.
0x101A
UINT16
R/W
1kh
1
100
Battery lifetime.
0x101B
UINT16
R/W
1
0
3
Ri alarm mode.
0: Disabled
1: Fix
2: Automatic
3: Automatic done
0x101C
UINT16
R/W
0.1mΩ
0
300
Ri nom.
0x101D
UINT16
R/W
1%
50
300
Ri max. variation.
0x1020
UINT16
R/W
1
1
2
Operating mode.
1: UPS
2: DC/DC
0x1021
UINT16
R/W
0.1
10
58
Nominal output voltage.
0x1022
UINT16
R/W
0.1
5
21
Max. input current.
0x1023
UINT16
R/W
0.1
1
21
Max. output current.
0x1024
UINT16
R/W
1
0
1
Max. Backup time enable.
0: Disabled
1: Enabled
0x1025
UINT16
R/W
1m
1
1440
Max. backup time.
0x1026
UINT16
R/W
1
0
1
Buzzer enable.
0: Disabled
1: Enabled
0x1027
UINT16
R/W
1
0
65535
Relay 1 configuration (see §4.2.26).
0x1028
UINT16
R/W
1
0
65535
Relay 2 configuration (see §4.2.27).
0x1029
UINT16
R/W
1
1
2
Inhibit polarity.
1: Low
2: High
0x102A
UINT16
R/W
1
1
2
DC/DC output mode.
1: Single
2: Parallel
0x102B
UINT16
R/W
1
0
1
Output enable.
0: Disabled
1: Enabled
0x102C
UINT16
R/W
1
0
1
Aux enable.
0: Disabled
1: Enabled
0x1030
UINT16
R/W
1
0
1
PC shutdown enable.
0: Disabled
1: Enabled
0x1031
UINT16
R/W
1
0
1
PC automatic restart enable.
0: Disabled