Installation / Adjustment
Description of functions – Expansion card 12
Quick guide – menu settings
for passive cooling with 2 pipe system
Menu 9.1.10 Cooling [S]
The type of cooling system is set here. Selectable modes
are: ”PCAC 4pipes” “Off”, ”HPAC base card”, ”HPAC
expansion card 11”, ”Cooling accumulator”, “PKM 2
pipes” and “PKM 4 pipes”. The factory setting is “Off”.
Select “PKM 2 pipes”.
Menu 6.4.1 Cooling [U]
The cooling functions can be set to “On” or “Off” here.
The factory setting is “Off”.
Menu 6.4.2 Cooling curve [U]
The selected curve slope (cooling curve) is shown here.
The value can be set between 1 and 3.
The factory setting is 2.
Menu 6.4.3 Offset cold curve [U]
The selected cooling curve offset is shown here. The value
can be set between -10 and +10. The factory setting is 0.
Menu 6.4.4 Start temp. heating [U]
Outdoor temperature (menu 4.0) at the outdoor sensor
(UG) when the heat pump is permitted to produce heat.
The value can be set between 0 and 30 °C.
The factory setting is 20 °C.
Menu 6.4.5 Start temp. cooling [U]
Outdoor temperature (menu 4.0) at the outdoor sensor
(UG) when the heat pump is permitted to produce cool-
ing. The value can be set between 0 and 30 °C.
he factory setting is 25 °C.
Menu 6.4.9 Min. flow temp. [U]
The lowest flow temperature in cooling mode.
The value is adjustable between 2 and 65 °C.
The factory setting is 5 °C.
Menu 6.4.10 Period time shunt [U]
The time period for the shunt (SV-K) is chosen here.
Adjustable between 1 and 500 seconds.
The factory setting is 60 seconds.
Menu 6.4.11 Shunt intensification. [U]
The amplification for the shunt (SV-K) is chosen here. For
example, a 2 degree difference between the flow line
and the calculated flow line with 5 in amplification gives
10 secs/min controlling the shunt. The value can be set
between 1 and 10. The factory setting is 1.
Menu 6.4.12 Time betw. heat cold [U]
The time the heat pump must wait between production
of heat and cooling is set here. The value can be set be-
tween 0 and 10 hours. The factory setting is 3 hours.
The outline diagram with docking instructions is
available at www.nibe.eu