If unsure about applicable settings, contact your network
administrator (or similar) for further information.
Setting
1.
Tick “use proxy" if you do not want to use a proxy.
2.
Mark “server" and press the OK button.
3.
Enter the correct details via the virtual keypad.
4.
Select "OK" and press the OK button.
5.
Repeat 1 - 3 for "port", "user name" and "password".
6.
Mark “confirm" and press the OK button.
TIP
All settings made since opening the menu can
be reset by marking "reset" and pressing the
OK button.
MENU 4.1.4 - SMS (ACCESSORY IS RE-
QUIRED)
Make settings for the accessory SMS 40 here.
Add the mobile numbers that are to have access to
change and receive status information from the heat
pump. Mobile numbers must include country code e.g.
+46 XXXXXXXX.
If you want to receive an SMS message in the event of
the alarm mark the box to the right of the telephone
number.
NOTE
Telephone numbers provided must be able to
receive SMS messages.
MENU 4.1.5 - SG READY
This function can only be used in mains networks that
support the "SG Ready"-standard .
Make settings for the function "SG Ready" here.
affect room temperature
Here you set whether room temperature should be af-
fected when activating "SG Ready".
With low price mode on "SG Ready" the parallel offset
for the indoor temperature is increased by "+1". If a room
sensor is installed and activated, the desired room
temperature is instead increased by 1 °C.
With over capacity mode on "SG Ready" the parallel
offset for the indoor temperature is increased by "+2".
If a room sensor is installed and activated, the desired
room temperature is instead increased by 2 °C.
affect hot water
Here you set whether the temperature of the hot water
should be affected when activating "SG Ready".
With low price mode on "SG Ready", the stop temperat-
ure for the hot water is set as high as possible with
compressor operation only (immersion heater not per-
mitted).
With over capacity mode of "SG Ready" the hot water
is set to "luxury" (immersion heater permitted).
affect cooling (accessory required)
Here you set whether room temperature during cooling
operation should be affected when activating "SG
Ready".
With low price mode of "SG Ready" and cooling opera-
tion the indoor temperature is not affected.
With over capacity mode on "SG Ready" and cooling
operation, the parallel offset for the indoor temperature
is reduced by "-1". If a room sensor is installed and activ-
ated, the desired room temperature is instead reduced
by 1 °C.
affect pool temperature (accessory is required)
Here you set whether pool temperature should be af-
fected when activating "SG Ready".
With low price mode on "SG Ready", the desired pool
temperature (start and stop temperature) is increased
by 1 °C.
With over capacity mode on "SG Ready" the desired pool
temperature (start and stop temperature) is increased
by 2 °C
MENU 4.1.6 - SMART PRICE ADAPTION™
activated
This function can only be used if you have an hourly
tariff agreement with your electricity supplier that
supports Smart price adaption™ and you have an
activated NIBE Uplink account.
area
Here you select where (which zone) the heat pump
is set-up.
Contact your electricity supplier to find out which
zone digit to enter.
affect room temperature
Setting range: 1 - 10
Factory setting: 5
affect hot water
Setting range: 1 - 4
Factory setting: 2
25Chapter 3 | Control - MenusNIBE F1345