speed passive cooling EP14 (accessory
required)
Setting range: 1 - 100 %
Factory setting: 75 %
speed passive cooling EP15 (accessory
required)
Setting range: 1 - 100 %
Factory setting: 75 %
speed active cooling EP14 (accessory
required)
Setting range: 1 - 100 %
Factory setting: 75 %
speed active cooling EP15 (accessory
required)
Setting range: 1 - 100 %
Factory setting: 75 %
speed in wait mode, cooling, EP14
Setting range: 1 - 100 %
Factory setting: 30 %
speed in wait mode, cooling, EP15
Setting range: 1 - 100 %
Factory setting: 30 %
temperature difference, active cooling
Setting range: 2 - 10 °C
Factory setting: 5 °C
This menu is only displayed if you have a F1345 24 or
30 kW.
Set the speed of the brine pumps for this heat pump
here. Select "auto" if the speed of the brine pumps are
to be regulated automatically (factory setting) for optimal
operation.
For manual operation of the brine pumps, deactivate
"auto" and set the value to between 0 and 100 %.
For operation of brine pumps with “fixed delta”, select
“fixed delta” under “op. mode” and set the value
between 2 and 10 °C.
If there are accessories for cooling, you can also set the
brine pump’s speed during passive cooling operation
here (the brine pump then runs in manual operation).
This menu is also set in the slave heat pump's limited
menu system.
MENU 5.1.10 - OP. MOD HEAT MED PUMP
op. mode
Setting range: auto, intermittent
Default value: intermittent
Set the operating mode of the brine pumps for this heat
pump here.
This menu is also set in the slave heat pump's limited
menu system.
auto: The heating medium pumps run according to the
current operating mode for F1345.
intermittent: The heating medium pumps start 20
seconds before, and stop at the same time, as the
compressor.
MENU 5.1.11 - PUMP SPEED HEATING
MEDIUM
Operating status
Setting range: auto / manual
Default value: auto
Manual setting, hot water
Setting range: 1 - 100 %
Factory setting: 70 %
Manual setting, heating
Setting range: 1 - 100 %
Default values: 70 %
Manual setting, pool
Setting range: 1 - 100 %
Default values: 70 %
speed in wait mode
Setting range: 1 - 100 %
Default values: 30 %
min. allowed speed
Setting range: 1 - 50%
Default values: 1 %
max. allowed speed
Setting range: 50 - 100 %
Default values: 100 %
NIBE F1345Chapter 3 | Control - Menus34