speed active cooling (accessory is required)
Setting range: 1 - 100 %
Default values: 70 %
speed passive cooling (accessory is required)
Setting range: 1 - 100 %
Default values: 70 %
Set the speed at which the heat pumps are to operate
in the present operating mode for this heat pump. Select
"auto" if the speed of the heating medium pump is to
be regulated automatically (factory setting) for optimal
operation.
If "auto" is activated for heating operation, you can also
make the setting "max. allowed speed" which restricts
the heating medium pumps and does not allow them
to run at a higher speed than the set value.
For manual operation of the heating medium pumps
deactivate "auto" for the current operating mode and set
the value to between 0 and 100% (the previously set
value for "max. allowed speed" no longer applies).
"heating" means heating operating mode for the heating
medium pumps.
"speed in wait mode" means heating or cooling operating
mode for the heating medium pumps, but when the
heat pump has neither a need for compressor operation
nor electric additional heat and slows down.
This menu is also set in the slave heat pump's limited
menu system.
"hot water" means hot water operating mode for the
heating medium pumps.
"pool" means pool heating operating mode for the heat-
ing medium pumps.
"cooling" means cooling operating mode for the heating
medium pumps.
If there are accessories for cooling present or if the heat
pump has a built-in function for cooling you can also set
the heating medium pump speed during active respect-
ively cooling operating modes (the heating medium
pump then runs in manual operation).
MENU 5.1.12 - ADDITION
Make settings for connected additional heat (step con-
trolled or shunt controlled additional heat) here.
Select whether step controlled or shunt controlled addi-
tional heat is connected. Then you can make settings
for the different alternatives.
add.type: step controlled
add. heat in tank
Setting range: on/off
Factory setting, fuse: off
max step
Setting range (binary stepping deactivated): 0 – 3
Setting range (binary stepping activated): 0 – 7
Default value: 3
binary stepping
Setting range: on/off
Factory setting, fuse: off
fuse size
Setting range: 1 - 400 A
Factory setting: 16 A
transformation ratio
Setting range: 300 - 3000
Factory setting, fuse: 300
Select this option if the step controlled additional heat
is connected and is positioned before or after the revers-
ing valve for hot water charging (QN10). Step controlled
additional heat is for example an external electric boiler.
When binary stepping is deactivated (off), the settings
refer to linear stepping.
Here you can set the maximum number of permitted
additional heat steps, if there is internal additional heat
in the tank (only accessible if the additional heat is posi-
tioned after QN10), whether binary stepping is to be
used and the size of the fuse.
35Chapter 3 | Control - MenusNIBE F1345