Connecting refrigerant pipes
(not supplied)
Install the refrigerant pipes between the outdoor module
AMS 10 and HBS 05.
Installation must be carried out in accordance with cur-
rent norms and directives.
Parameters AMS 10
■
Maximum pipe length, AMS 10 (L): 30 m.
■
Maximum height difference (H): ±7m.
Pipe dimensions and materials
AMS 10-6
Liquid pipeGas pipe
Ø6.35 mm (1/4")Ø12.7 mm (1/2")Pipe dimension
Flare - (1/4")Flare - (1/2")Connection
Copper quality SS-EN 12735-1 or
C1220T, JIS H3300
Material
0.8 mm1.0 mmMinimum material
thickness
AMS 10-8, AMS 10-12 and AMS 10-16
Liquid pipeGas pipe
Ø9.52 mm (3/8")Ø15.88 mm (5/8")Pipe dimension
Flare - (3/8")Flare - (5/8")Connection
Copper quality SS-EN 12735-1 or
C1220T, JIS H3300
Material
Liquid pipeGas pipe
0.8 mm1.0 mmMinimum material
thickness
HBS 05Chapter 4 | Pipe connections16