Pipe connection
Pipe connection, refrigerant pipe
■
Perform pipe installation, on the refrigerant side
between outdoor module (AMS 10) and SPLIT box
(HBS 05), with the service valves (QM35, QM36) closed.
■
Connect refrigerant pipes between the service valves
(QM35 and QM36) on the outdoor module (AMS 10)
and the connections (XL52 and XL53) on SPLIT box
(HBS 05).
■
Ensure that water or dirt does not enter the pipes.
■
Bend the pipes with as large a radius as possible (at
least R100~R150). Do not bend a pipe repeatedly. Use
a bending tool.
■
Connect the flare connector and tighten to the follow-
ing torque. Use the "Tightening angle" if a torque
wrench is not available.
Recommen-
ded tool
length
(mm)
Tightening
angle (°)
Tightening
torque
(Nm)
Outer dia-
meter, cop-
per pipe
(mm)
15045~6014~18Ø6.35
20030~4534~42Ø9.52
25030~4549~61Ø12.7
30015~2068~82Ø15.88
NOTE
Gas shielding must be used when soldering.
Flare connections
Expansion:
A (mm)Outer diameter, copper pipe (mm)
9.1Ø6.35
13.2Ø9.52
16.6Ø12.7
19.7Ø15.88
Ejection:
B, with a conven-
tional tool (mm)
B, with an
R410A tool
(mm)
Outer diameter,
copper pipe
(mm)
1.0~1.50.0~0.5Ø6.35
0.7~1.30.0~0.5Ø9.52
1.0~1.50.0~0.5Ø12.7
0.7~1.30.0~0.5Ø15.88
(Follow instructions for the tool used.)
17Chapter 4 | Pipe connectionsHBS 05