Pipe coupling heating medium
circuit
■
HBS 05 is intended for combination with NIBE outdoor
module (AMS 10) and NIBE indoor module (VVM) or
control module (SMO), in accordance with one of the
system solutions that can be downloaded from the
website www.nibe.eu.
■
Install vent valves if the pipe routing requires this to
avoid malfunctions.
■
Install the supplied particle filter before the inlet, i.e.
the connection (XL2, HM return) on HBS 05.
■
Install the enclosed condensation hose (WP3).
TIP
Position the condensation hose in the
grooves on the underside of HBS 05, either
the right or the left hand side or at the back.
Pressure drop, heating medium
side
HBS 05
0
5
10
15
20
25
30
0,0
0,1 0,2 0,3 0,4 0,5 0,6 0,7 0,8
Flöde [l/s]
Tryc
kfall [kPa]
Tryckfall HBS05
HBS05-6, -16HBS05-12
Pressure drop HBS05
Pressure drop
[kPa]
Flow [l / s]
Docking alternatives
HBS 05 can be installed in several different ways. The
required safety equipment must be installed in accord-
ance with current regulations for all docking options. To
ensure fault-free operation of the system, it is recommen-
ded to give consideration to the values according to the
table when adjusting the system.
See www.nibe.eu for more docking options.
Installation requirements
HBS 05-16HBS 05-12HBS 05-12HBS 05-6SPLIT box HBS 05
AMS 10-16AMS 10-12AMS 10-8AMS 10-6Compatible outdoor module
Requirements
0.6 MPa (6 Bar)Max pressure, climate system
55 / 45°CHighest recommended supply/return temperat-
ure at dimensioned outdoor temperature
58 °CMax flow line temperature with compressor
7 °CMin supply temperature cooling, HBS 05
25 °CMax supply temp. cooling
0.39 l/s0.29 l/s0.19 l/s0.19 l/sMin flow, climate system, 100 % circulation
pump speed (defrosting flow)
Recommendations
150 l80 l50 l20 lMin volume, climate system during heating,
cooling*
150 l100 l80 l50 lMin volume, climate system during under floor
cooling*
0.79 l/s0.57 l/s0.38 l/s0.29 l/sMax flow, climate system
0.24 l/s0.15 l/s0.12 l/s0.09 l/sMin flow, heating system
0.32 l/s0.20 l/s0.16 l/s0.11 l/sMin flow, cooling system
*Refers to circulating volume.
19Chapter 4 | Pipe connectionsHBS 05