28 Unidrive M400 Quick Start Guide
Issue Number: 8
00.024
Customer Defined
Scaling
0.000 to 10.000 1.000 RW Num US
00.025 User Security Code 0 to 9999 0 RW Num ND PT US
00.027
Power-up Keypad
Control Mode
Reference
Reset (0), Last (1), Preset (2) Reset (0) RW Txt US
00.028 Ramp Mode Select
Fast (0), Standard (1),
Std boost (2), Fast boost (3)
Standard (1) RW Txt US
00.029 Ramp Enable
Off (0) or On (1) On (1) RW Bit US
00.030 Parameter Cloning
None (0), Read (1), Program (2),
Auto (3), Boot (4)
None (0) RW Txt NC US
00.031 Stop Mode
Coast (0),
Ramp (1),
Ramp dc I (2),
dc I (3),
Timed dc I (4),
Disable (5)
Coast (0),
Ramp (1),
Ramp dc I (2),
dc I (3),
Timed dc I (4),
Disable (5),
No Ramp (6)
Ramp (1) RW Txt US
00.032
Dynamic V to F
Select / Flux
Optimization Select
0 to 1 0 RW Num US
00.033
Catch A Spinning
Motor
Disable (0), Enable (1),
Fwd Only (2), Rev Only (3)
Disable (0) RW Txt US
00.034 Digital Input 5 Select
Input (0), Therm Short Cct (1),
Thermistor (2), Therm No Trip (3)
Input (0) RW Txt US
00.035
Digital Output 1
Control
0 to 21 0 RW Num US
00.036
Analog Output 1
Control
0 to 14 0 RW Txt US
00.037
Maximum Switching
Frequency
0.667 (0), 1 (1),
2 (2), 3 (3), 4 (4),
6 (5), 8 (6), 12 (7),
16 (8) kHz
2 (2), 3 (3),
4 (4), 6 (5),
8 (6), 12 (7),
16 (8) kHz
3 (3) kHz RW Txt US
00.038 Autotune 0 to 2 0 to 3 0 RW Num NC US
00.039
Motor Rated
Frequency
0.00 to 550.00 Hz
50Hz: 50.00 Hz
60Hz: 60.00 Hz
RW Num US
00.040
Number of Motor
Poles***
Auto (0) to 32 (16) Auto (0) RW Num US
00.041 Control Mode
Ur S (0), Ur (1),
Fixed (2),
Ur Auto (3),
Ur I (4),
Square (5),
Fixed Tapered (6)
Ur I (4) RW Txt US
00.042
Low Frequency
Voltage Boost
0.0 to 25.0 % 3.0 % RW Num US
00.043 Serial Baud Rate
600 (1), 1200 (2),
2400 (3), 4800 (4), 9600 (5),
19200 (6), 38400 (7), 57600 (8),
76800 (9), 115200 (10)
19200 (6) RW Txt US
00.044 Serial Address 1 to 247 1 RW Num US
00.045
Reset Serial
Communications
Off (0) or On (1) Off (0) RW ND NC US
00.046
Brake Controller
Upper Current
Threshold
0 to 200 % 50 % RW Num US
00.047
Brake Controller
Lower Current
Threshold
0 to 200 % 10 % RW Num US
Parameter
Range
() Default ()
Type
OL RFC-A OL RFC-A

Other manuals for Nidec Unidrive M400 series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nidec Unidrive M400 series and is the answer not in the manual?

Nidec Unidrive M400 series Specifications

General IconGeneral
BrandNidec
ModelUnidrive M400 series
CategoryController
LanguageEnglish

Related product manuals