Ventilation at times of low outdoor air temperature
I
t is possible to prevent low humidity in the home by reducing ventilation in case of low outdoor
temperatures. This function is particularly useful in countries with heavy frosts and at high altitudes
where the outdoor air is very dry.
The function can also be used if no after-heating element has been fitted, and the supply air feels too
cold in case of low outdoor air temperature. Lower ventilation levels will increase temperature
efficiency and thus raise the supply air temperature slightly.
The Compact P heat pump is able to heat supply air up to 34 °C in periods where no domestic hot water
is produced.
Ventilation
Low outdoor temperature settings
↳
Low fan speed at low outdoor temp. Settings:
Standard setting:
Description:
On / Off
Off
This indicates whether it is wished to operate at low
fan speed in case of low outdoor temperature.
↳
Below outdoor temperature (°C) Settings:
Standard setting:
Description:
-20 ↔ 10 °C
0 °C
This indicates the outdoor temperature at which it is
wished to start the low fan speed.
↳
Fan speed Settings:
Standard setting:
Description:
Level 1/ Level 2
Level 1
This indicates at what fan speed the unit should run in
case of low outdoor temperatures.
Prioritisation sequence in the control system:
1. User selection 2 and 1 with high priority for ventilation
2. High ventilation in connection with cooling
3. Low ventilation in connection with low outdoor air
temperature
4. Low air humidity
5. High air humidity
6. Userprogram 2
7
. Userprogram 1
8. CO2
2
level (accessory)
9. Manually set values
10. Weekprogram