Temperature regulation
↳
Master sensor indoor room
temperature
Settings:
Standard setting:
Description:
T3 / TExt
T3
Here it is selected which temperature sensor is used
for measuring the room temperature.
T3 the temperature sensor in the extract air.
TExt external temperature sensor located in the
dwelling (not a Nilan supply).
↳
Temperature regulatory deadband (°C) Settings:
Standard setting:
Description:
0 ↔ 10°C
1°C
Here the regulatory deadband is set for temperature
regulation.
↳
Temperature offset bypass (°C) Settings:
Standard setting:
Description:
0 ↔ 10°C
0°C
Here is set when the bypass damper is to open,
thereby diverting the air past the heat exchanger.
(Room temperature setpoint + Regulatory deadband +
Offset bypass damper)
The bypass damper only opens if the outdoor
temperature is lower than the indoor temperature
External heating regulation
↳
Deadband external room heating (°C) Settings:
Standard setting:
Description:
0 ↔ 10°C
1°C
The unit can control an external heat supply by sending
a release or blocking signal. The regulatory deadband
for the control system is set here.
Regulation of external heat source
Permanent setting 1°C
20°C
Room temperature ˂
18°C releases external heat supply
Room temperature ˂
19°C blocks external heat supply
Regulatory deadband for external heating (ºC)
Compact P / Compact P Polar (English)