De-icing the heat pump:
De-icing heat pump
Evaporator de-icing by T6 Settings:
Standard setting:
Description:
On / Off
On
Activates or deactivates de-icing function for the heat
pump.
Maximum time de-icing (min) Settings:
Standard setting:
Description:
1 30 minutes
10 minutes
Indicates the maximum de-icing time for the heat
pump.
Minimum time between de-icing
(min)
Settings:
Standard setting:
Description:
1 180 minutes
30 minutes
Indicates the minimum time between de-icing
processes in the heat pump.
Start temperature de-icing (ºC) Settings:
Standard setting:
Description:
-15 0°C
-2°C
Indicates the evaporator temperature (T6) at which
de-icing of the heat pump is to start.
Stop temperature de-icing (ºC) Settings:
Standard setting:
Description:
0 15°C
C
Indicates the evaporator temperature (T6) at which
de-icing of the heat pump is to stop.