User program 2
↳
Running time (min) Settings:
Standard setting:
Description:
0 ↔ 480 minutes
0 minutes
Here it is set how long the program is to run after the
external signal has stopped.
Hence, when connecting a cooker hood, it is
recommended to set it to 0 hours, so the unit returns
to normal operation when the cooker hood is turned
off and the external signal is removed.
↳
Program setting Settings:
Standard setting:
Description:
Auto/ Night setback/ Fans only
Auto
Here the program is selected which it is wished to run.
↳ Set point room temperature (°C) Settings:
Standard setting:
Description:
5 ↔ 40 °C
20 °C
Here the desired room temperature is set.
↳ Set point, hot water (°C) Settings:
Standard setting:
Description:
10 ↔ 60 °C
36 °C
Here the desired temperature for the domestic hot
water is set.
↳
Fan speed level Settings:
Standard setting:
Description:
Level 1/ Level 2/ Level 3/ Level 4
Level 1
Here the desired fan speed level is selected.
↳ High priority fan speed Settings:
Standard setting:
Description:
On / Off
Off
Here it is selected whether the fan settings should
override all other settings, such as humidity low,
humidity high and winter low.
Prioritisation sequence in the control system:
1. U
serprogram 2 and 1 with high priority for ventilation
2. High ventilation in connection with cooling
3. Low ventilation in connection with low outdoor air
temperature
4. Low air humidity
5. High air humidity
6. U
serprogram 2
7. Userprogram 1
8. CO2
2
level (accessory)
9. Manually set values
10. Weekprogram
38