Safety group with scald protection
As standard, the control system has a temperature limit for domestic hot water of 65 ºC. This prevents
users from scalding themselves when turning on the hot water.
This means that when VP18 (Cooling model) is in cooling mode, cooling will cease when the domestic hot
water reaches a temperature of 65 ºC.
Should the cooling requirement be higher than this, the temperature limit may be raised to 80 ºC. If
doing so, you must install a scald protection device under the hot water tank to prevent users from
scalding themselves when turning on the hot water.
The scald protection device mixes hot water with cold water. This lowers the temperature and scalding
is avoided. This will extend the cooling period of the VP18 (Cooling model).
CAUTION
If you connect a solar panel to the hot water tank, you must install a scald protection device.
1
2
3
4
5
6
7
8
1. Hot water from the hot water tank
2. Cold water to the hot water tank
3. Stopcock cold water
4. Pressure relief valve (6 bar or 10 bar)
5. Overflow from the safety valve is led to a visible drain
6. Cold water supply
7. Domestic hot water for the dwelling
8. Mixing valve for domestic hot water for the dwelling (can be set between 35 - 60 ºC)
28

Other manuals for nilan CTS602 HMI

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the nilan CTS602 HMI and is the answer not in the manual?

nilan CTS602 HMI Specifications

General IconGeneral
Brandnilan
ModelCTS602 HMI
CategoryFan
LanguageEnglish

Related product manuals