EasyManuals Logo

Nord Drivesystems SK 511E Series User Manual

Nord Drivesystems SK 511E Series
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #53 background imageLoading...
Page #53 background image
6 Operating status messages
BU 0540 EN-1516 53
E020
E021
20.0 Reserved
System error in program execution, triggered by EMC
interference.
Observe wiring guidelines
Use additional external mains filter.
FI must be very well earthed.
20.1 Watchdog
20.2 Stack overflow
20.3 Stack underflow
20.4 Undefined opcode
20.5 Protected Instruct.
"Protected Instruction"
20.6 Illegal word access
20.7 Illegal Inst. Access
"Illegal instruction access"
20.8 Program memory error
"Program memory error"
(EEPROM error)
20.9 Dual-ported RAM
21.0 NMI error
(Not used by hardware)
21.1 PLL error
21.2 ADU error "Overrun"
21.3 PMI error "Access Error"
21.4 Userstack overflow
Pos: 471 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ Fehl er E0 22 "r es er vie rt" - PLC [S K 180E ... SK 5xxE] @ 2\mod_1361527702934_388.docx @ 59091 @ @ 1
E022
--- Reserved
Error message for PLC see supplementary instructions
BU 0550
Pos: 47 2 /Anlei tung en/El ektr onik/FU und Star ter/6 . Meld ungen zum Betr iebsz usta nd/Stör mel dung en (Aufli st ung)/ Fehl er E0 23 "r es ervi ert" - PLC [SK 180 E ... SK 5xxE] @ 2\mod_1361527808170_388.docx @ 59116 @ @ 1
E023
--- Reserved
Error message for PLC see supplementary instructions
BU 0550
Pos: 473 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ Fehl er E0 24 "r es er vie rt" - PLC [S K 180E ... SK 5xxE] @ 6\mod_1423644411761_388.docx @ 201828 @ @ 1
E024
--- Reserved
Error message for PLC see supplementary instructions
BU 0550
Pos: 475 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /War n meldu nge n (T abel le nüb ersc hri ft) @ 3 \mod_1361803463080_388.docx @ 59898 @ 5 @ 1
Warning messages
Display in the
SimpleBox / ControlBox
Warning
Text in the ParameterBox
Cause
Remedy
Group Details in P700
[-02]
Pos: 476 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 001 [SK 180 E ... SK 5xxE] @ 2\ mod_1347456220101_388.docx @ 46975 @ @ 1
C001
1.0 Overtemp. Inverter
"Inverter overtemperature"
(inverter heat sink)
Inverter temperature monitoring
Warning: permissible temperature limit reached.
Reduce ambient temperature
Check the FI fan / control cabinet ventilation
Check the FI for dirt
Pos: 477 /A nleit ung en/El e ktr onik /FU und Star ter /6. M eldung en zu m B etrie bsz ust and /Stör m eld ung en (A ufli st ung)/ W arnung C 002 [SK 180 E/SK 2x xE/SK 5xx E] @ 2\mod_1347456223954_388.docx @ 47000 @ @ 1
C002
2.0 Overtemp. Motor PTC
"Overtemperature motor
thermistor "
Warning from motor temperature sensor (triggering
threshold reached)
Reduce motor load
Increase motor speed
Use external motor fan
2.1 Overtemp. Motor I²t
"Motor overtemperature I²t"
Only if I
2
t motor (P535) is
programmed.
Warning: I2t- motor monitoring (1.3 times the rated current
reached for the time period specified in (P535))
Reduce motor load
Increase motor speed

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Nord Drivesystems SK 511E Series and is the answer not in the manual?

Nord Drivesystems SK 511E Series Specifications

General IconGeneral
BrandNord Drivesystems
ModelSK 511E Series
CategoryDC Drives
LanguageEnglish

Related product manuals