5 Parameters 
BU 0505 EN-3021    135 
Pos: 299 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P480. ..P481 – Verwendung der Merker  @ 6\mod_1422968583767_3 88.docx @ 201078 @  @ 1 
 
P480 … P481  Using flags 
  With the aid of the two flags it is possible to define simple, logical sequences of functions. 
To do this, the "triggers" for a function (e.g. a motor PTC overtemperature warning) are defined in 
parameter (P481) in arrays [-07] - "Flag 1" or [-08] - "Flag 2"  
As well as this, the function which the frequency inverter is to execute when the "trigger" 
- i.e. the response by the frequency inverter is defined in parameter (P480) in arrays [-09] or [-
10]. 
 
Example: 
In an application, if the temperature of the motor reaches the overtemperature range 
("Overtemperature motor PTC") the frequency 
inverter is to immediately reduce the speed to a 
specific speed (e.g. by means of an active fixed frequency). This is to be implemented by 
"Deactivation of analog input 1" via which in this example, the actual setpoint is normally set. 
This is used to redu
ce the load on the motor, so that the temperature can stabilise or the drive 
unit reduces speed to a defined value before a shut-down due to error is made. 
 
Step  Description  Function 
1 
Set Flag 1 to the "Motor overtemperature" function 
2 
Set Flag 1 to the function "Setpoint 1 On/Off 
 
It should be noted that depending on the function which is selected in (P481) the function may 
need to be inverted by modification of the standardisation (P482).  
Pos: 300 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400-P499/Parameter P482 – Normierung B us I/O Out Bits [SK 5xxE] @ 0\mod_13280 02779143_388.doc x @ 10825 @  @ 1 
 
P482  [-01] 
  ... 
  [-10]
Norm. BusIO Out Bits 
(Scaling of bus I/O Out bits)  
 
S   
-400…400 % 
{ all 100 } 
 
Adjustment of the limit values of the relay functions/Bus Out Bits. For a negative value, the output 
function will be output negative.  
When the limit value is reached and the setting values are positive, the relay contact closes, with 
negative setting values the relay contact opens. 
The assignment of the arrays correspond to those of parameter (P481). 
Pos: 301 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P400- P499/Parameter P483 – Hyster ese Bus I/O Out Bits [SK 5xxE] @ 0\mod_1328002828441_ 388.docx @ 10848 @  @ 1 
 
P483  [-01] 
  ... 
  [-10]
Hyst. BusIO Out Bits 
(Hysteresis of bus I/O Out bits)  
 
S   
1…100 % 
{ all 10 } 
 
Difference between switch-on and switch-off point to prevent oscillation of the output signal. 
The assignment of the arrays correspond to those of parameter (P481). 
 
Pos: 302 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ P5xx Zusatzparamet er @ 0\mod_1328091531180_388. docx @ 10880 @ 5 @ 1