7 Technical data
BU 0505 EN-3021 177
7.3 Electrical data
The following tables contain the data which is relevant for UL.
Details of the UL/cUL approval conditions can be found in Section 1.7. Use of mains fuses which are
faster than those stated is permissible.
By the use of a mains choke, the input current is reduced to approximately that of the output current
( Section 2.7.1 "Mains chokes").
Pos: 492 /Anleitungen/ Elektronik/F U und Starter/7. Technische Da ten/SK 5xxE/Elektr ische Daten 115V [SK 5xxE] @ 6\mod_1413356648138_38 8.docx @ 155174 @ 3 @ 1
7.3.1 Electrical data 115 V
Frequency inverter type SK 5xxE…
-250-112- -370-112- -550-112- -750-112- -111-112-
1 1 1 1 1
Nominal motor power
(4-pole standard motor)
230 V
0.25 kW 0.37 kW 0.55 kW 0.75 kW 1.10 kW
240 V
1
/
3
hp ½ hp ¾ hp 1 hp 1 ½ hp
Mains voltage
115 V
1 AC 100 … 120 V, ± 10 %, 47 … 63 Hz
Input current
rms
8.9 A 11.0 A 13.1 A 20.1 A 23.5 A
FLA
8.9 A 10.8 A 13.1 A 20.1 A 23.5 A
Output voltage
230 V
3 AC 0 – 2x mains voltage
Typical output
rms
1.7 A 2.2 A 3.0 A 4.0 A 5.3 A
FLA
1.7 A 2.1 A 3.0 A 4.0 A 5.3 A
Min. brake resistor Accessories
240 Ω 190 Ω 140 Ω 100 Ω 75 Ω
Pulse frequency
range
3 – 16 kHz
Factory setting
6 kHz
Ambient temperature S1
40 °C 40 °C. 40 °C. 40 °C. 40 °C.
S3 80 %, 10 min
50 °C. 50 °C. 50 °C. 50 °C. 50 °C.
S3 70 %, 10 min
50 °C. 50 °C. 50 °C. 50 °C. 50 °C.
Type of ventilation
Free convection
Weight Approx. [kg]
1.4 1.8
General fuses (AC) (recommended)
slow-blowing
10 A 16 A 16 A 25 A 25 A
Isc
1)
[A]
UL fuses (AC) – permitted
Class
Fuse
J (600 V) x
10 A 13 A 20 A 25 A 25 A
CC, J, R, T, G, L (300 V)
x
10 A 20 A 20 A 25 A 20 A
Bussmann LPJ-
x
10SP 13SP 20SP 25SP 25SP
CB
(480 V)
x
15 A 15 A 20 A 25 A 20 A
1) Maximum permissible mains overload current
Pos: 493 /Anleitungen/ Elektronik/F U und Starter/7. Technische D aten/SK 5xxE/Elek trische Daten 230V [SK 5xxE] @ 6\mod_1413368025942_38 8.docx @ 155198 @ 3 @ 1