SK 54xEUsers Manual for Frequency Inverters
84 BU 0505 EN-3021
3.4 Connection of multiple device to a parameterisation tool
In principle it is possible to access several frequency inverters via the ParameterBox or the
NORD CON software. In the following example, communication is made via the parameterisation tool,
by tunnelling the protocols of the individual devices (max. 8) via the common system bus (CAN). The
following points must be noted:
1. Physical bus structure
Establish a CAN connection (system bus) between the devices (Terminal: X9 or X10 (Type: RJ
45))
2. Supply electricity (24 V) to the CAN bus. Establish the connection, for example via the RJ45
WAGO connection module (please see chapter 2.11 "RJ45 WAGO- Connection module")
3. Parameterisation
Parameter Settings on the inverter
No. Designation FI 1 FI 2 FI 3 FI 4 FI 5 FI 6 FI 7 FI 8
P503
Leading function output
4 (system bus active)
P512
USS address
0
0
0
0
0
0
0
0
P513
Telegram time-out (s)
0.6
0.6
0.6
0.6
0.6
0.6
0.6
0.6
P514
CAN bus baud rate
5 (250 kBaud)
P515
CAN bus address
32
34
36
38
40
42
44
46
To adopt the addresses, the 24 V supply of the CAN bus must be completely switched off
for approx. 30 sec.
4. Connect the parameterisation tool as usual via RS485 (Terminal: X11 (Type: RJ12)) to the first
frequency inverter.
Conditions / Restrictions:
a. In order to use the complete range of functions the first frequency inverter (FI 1) must at least
correspond to the firmware status 2.2 R0 (SK 54xE) or 3.0 R0 (all other SK 5xxE devices).
b. All other connected frequency inverters from the series must at least have a firmware status of
2.1 R0, in order to display the devices 5 … 8 correctly. Devices with a firmware version which is
older than 1.8 R0 do not have the required functionality.
c. If NORDCON is connected to an inverter other than FI 1, the status of FI 1 will be displayed as
"Not ready". The status of devices 5 8 will also be displayed as "Not ready" if they have a
software status which is older than 2.1 R0.
d. The parameterisation tools must also correspond to the latest software status:
NORDCON
≥ 02.03.00.21
ParameterBox
≥ 4.5 R3.
Pos: 113 /Anleitungen/ Elektronik/F U und Starter/4. Inbetriebna hme/SK 500E/4. Inbetri ebnahme @ 0\mod_13275 69589301_388.docx @ 7173 @ 1 @ 1