5 Parameters
BU 0505 EN-3021 95
the rotor resistance determined by measurement ((P220) Function 2)
the stray inductance determined by measurement ((P220)
Function 2)
63 =
the inductance determined by measurement ((P220) Function 2)
Pos: 125 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P000- P099/Parameter P002 – Di splay-Faktor @ 0\mod_132757 3818457_388.doc x @ 7409 @ @ 1
P002
Display factor
(Display factor)
S
0.01 ... 999.99
{ 1.00 }
The selected operating value in parameter P001 >Select of display< is multiplied with the scaling
factor in P000 and displayed in >Operating parameter display<.
It is therefore possible to display system-specific operating such as e.g. the throughput quantity
Pos: 126 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P000- P099/Parameter P003 – Super visor-Code @ 0\mod_1327 573882472_388.doc x @ 7432 @ @ 1
P003 Supervisor Code
(Supervisor Code)
0 ... 9999
{ 1 }
0 = The Supervisor parameters are not visible.
1 = All parameters are visible.
2 = Only the menu group 0 > Operating display< (P000 … P003) is visible.
3 ... 9999, as for setting value 2.
Information
Display via NORD CON
If parameterisation is carried out with the NORD CON software, the settings 2 ... 9999 the
settings are as for the 0 setting.
Pos: 127 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ P1xx Basisparameter @ 0\mod_1327574618174_ 388.docx @ 7458 @ 5 @ 1
Basic parameters
Parameter
{factory setting}
Setting value / Description / Note Supervisor
Parameter
set
Pos: 128 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P100- P199/Parameter P100 – Par ametersatz @ 0\mod_13275747 57831_388.doc x @ 7481 @ @ 1
P100
Parameter set
(Parameter set)
S
0 ... 3
{ 0 }
Selection of the parameters sets to be parameterised. 4 parameter sets are available. The
parameters to which different values can also be assigned in the 4 parameter sets are known as
"parameter set-dependent" and are marked with a "P" in the header in the following descriptions.
The operating parameter set is selected using appropriately parametrised digital inputs or by
means of BUS actuation.
If enabled via the keyboard (SimpleBox, ControlBox, PotentiometerBox or ParameterBox), the
operating parameter set will match the settings in P100.
Pos: 129 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P100- P199/Parameter P101 – Par am.-Satz kopieren @ 0\mod_1327 574829893_388.doc x @ 7504 @ @ 1
P101
Copy parameter set
(Copy parameter set)
S
0 ... 4
{ 0 }
After confirmation with the OK / ENTER key, a copy of the parameter set selected in P100
>Parameter set< is written to the parameter set dependent on the value selected here
0 = Do not copy
1 = Copy actual to P1: Copies the active parameter set to parameter set 1
2 = Copy actual to P2: Copies the active parameter set to parameter set 2
3 = Copy actual to P3: Copies the active parameter set to parameter set 3
4 = Copy actual to P4: Copies the active parameter set to parameter set 4
Pos: 130 /Anleitungen/ Elektronik/F U und Starter/5. Parameter/ Parameterauflis tung (P000 ...)/P100- P199/Parameter P102 – Hoc hlaufzeit @ 0\mod_13275 74880847_388.doc x @ 7527 @ @ 1