2 Assembly and installation
BU 0500 GB Subject to technical alterations 29
2.8.6 Jumper “A” mains input
In order to make the frequency inverter suitable for IT networks this jumper must be set to position 0.
Here it must be noted that the specified degree of radio interference suppression changes. Further details can
be found in Section 8.3. EMC.
= Operation in IT network = Position 0
= irrelevant = Position 1
= normal position = Position 2
2.8.7 Jumper “B” motor output
This jumper makes the device suitable for IT networks or reduces the leakage current of the frequency
inverter to earth. This may be necessary of several frequency inverters are operated via a single FI circuit
breaker.
Here it must be noted that the specified degree of radio interference suppression changes. Further details can
be found in Section 8.3. EMC.
= Operation in IT network = Position 0
= normal position = Position 1
= reduced leakage currentPosition 2
(The set pul se frequency (P504) onl y has
a slight in fluence on the lea kage current.)