4 Commissioning
BU 0500 GB Subject to technical alterations 65
4.2 Minimum configuration of control connections
If the frequency inverter is to be controlled via the digital and analog inputs, this can be implemented
immediately in the condition as delivered. Settings are not necessary for the moment.
Minimum circuitry
Basic parameters
If the current setting of the frequency inverter is not known, loading the default setting is recommended Æ
P523 = 1. The inverter is pre-programmed for standard applications in this configuration. If necessary, the
following parameters can be adjusted with the optional SimpleBox SK CSX-0 or ControlBox TY3-CTR:
Potentiometer, 10kOhm
(Function P400 = 1)
(min./max. range P104/105)
Switch, ON/OFF
(Function P420 = 1)
R = 10k
AIN 1
GND/0V
VO 10V
DIN 1
VO 15V
11
12
14
16
17
21
22
23
24
25
42
40
41
P0--
Display parameters
_ _ _ _
P1--
Basic parameters
P2--
Motor data
P4--
Control terminals
P5--
Ad dition a l param .
P7--
Information
As standard the
actual output frequency
is displayed
P102
Acceleratio n time
0 ... 320s
Motor data
See 4. 1 Basic set tings
P400
Function analog input
0...10V -frequency-
Operating values
display (or operational)
following mains ON
P103
Deceleration time
0 ... 320s
P104
Min. frequency
0 ... 400H z
P105
Max. frequency
0.1 ... 400Hz
P420
Funct. Digital input 1
- ON right -
P523
=1
Load default data