2.9.3 Details of the SK 5x5E control connections
Control voltage 24V external! Terminal 44. The frequency inverter must be supplied with an external 24V
supply.
Terminal Function
[factory setting]
Data Description / wiring suggestion Parameter
Terminal block X3 (See also Chap. 2.8)
1 K1.1
2 K1.2
Output 1
[Braking control]
Braking control P434...
3 K2.1
4 K2.2
Output 2
[Ready/Fault]
Relay closing contact
230V AC / 24V DC, 2A
Fault / Ready P441...
Terminal block X4
11 VO 10V 10V
Reference voltage
10V, 5mA
12 GND /0V Reference potential
for analogue signals
0V analogue
14 AIN1 Analog input 1
[set point frequency]
P400...
16 AIN2 Analog input 2
[no function]
V=0...10V, R
i
=30kΩ,
I=0/4...20mA, R
i
=250Ω,
can be switched over
with DIP switch,
reference voltage GND.
For the use of digital
functions 7.5...30V.
The analogue input controls the output
frequency of the frequency inverter.
R = 10k
11
12
14
16
17
The possible digital functions are
described in the parameters
P420...P425.
P405...
17 AOUT1 Analogue output
[no function]
0...10V
Reference potential GND
max. load current:
5mA analogue,
20mA digital
Can be used for an external display or
for further processing in a following
machine.
Datails of analogue/digital can be
found in Parameter P418
P418/419