88 Subject to technical alterations BU 0500 GB
Parameter Set value / Description / Note Device Supervisor
Parameter
set
P402 Analog input adjustment 1: 0%
S
-50.00 ... 50.00 V
[ 0.00 ]
This parameter sets the voltage that should correspond with the minimum value of the selected
function for the analog input 1. In the factory setting (setpoint) this value is equivalent to the
setpoint set via P104 >Minimum frequency<.
Typical setpoints and corresponding settings:
0 - 10 V Æ 0.00 V
2 - 10 V Æ 2.00 V (for function 0-10 V monitored)
0 - 20 mA Æ 0.00 V (internal resistance approx. 250Ω)
4 - 20 mA Æ 1.00 V (internal resistance approx. 250Ω)
P403 Analog input adjustment 1: 100%
S
-50.00 ... 50.00 V
[ 10.00 ]
This parameter sets the voltage that should correspond with the maximum value of the selected
function for the analog input 1. In the factory setting (setpoint) this value is corresponds with the
setpoint set via P105 >Maximum frequency<.
Typical setpoints and corresponding settings:
0 - 10 V Æ 10.00 V
2 - 10 V Æ 10.00 V (for function 0-10 V monitored)
0 - 20 mA Æ 5.00 V (internal resistance approx. 250Ω)
4 - 20 mA Æ 5.00 V (internal resistance approx. 250Ω)
P400 ... P403
P401 = 0 Æ 0 - 10V limited
0.0V
2.5V
5.0V
10.0V
P105
P104
P402
P403
outpu
t
frequenc
y
setpoint
voltage
positive
P401 = 1 Æ 0 - 10V not limited
0.0V
2.5V
5.0V
10.0V
P105
P104
P402
P403
outpu
t
frequenc
y
setpoint
voltage
positive
ne
g
ative
P404 Filter analog input 1
S
1 ... 400 ms
[ 100 ]
Adjustable digital low-pass filter for the analog signal. Interference peaks are hidden, the reaction
time is extended.
P405 Analog input function 2
P
0 ... 82
[ 0 ]
This parameter is identical to P400.