Fire/Security Applications Section 4 Applications
NFS-3030 Installation PN 51330:C 10/28/2003 59
Figure 43 Typical Connections for an NBG-12LRA Agent Release-Abort Station
Note: See Circuit Requirements for Section 4.7 “Connecting a Releasing Device to a FCM-1 Module”
on page 58.
Note: Devices for use in releasing applications must be programmed as type code RELEASE CIRCUIT
or REL CKT ULC.
+
+
–
–
–
–
+
+
+
1
2
4
6
5
7 -
6 +
1
2
3
4
0
–
–
+
+
–
–
+
+
SLC loop to FACP,
LCM-320, or LEM-320
FCM-1
FRM-1
FMM-101
FMM-101
Black
Red
Yellow
Violet
Black
Red
Yellow
Violet
Non-resettable +24 VDC
from AMPS-24/E
Manual Abort
Manual Release
Normal
Release
NBG-12LRA
See Document 51369
for installation details.
ELR mode R-47K
supervised and
power-limited
RedBrown
24 VDC UL-listed
releasing device
C.
N.O.
REL-47K
(use with Type Code
“Rel Ckt ULC”)
3030-NBG12LRA.wmf
System
Common (–)
24 VDC power
from FACP’s
main power supply
N.C.